Fluke 1773/Basic Power Quality Analyzer (No probes)
The Fluke 1773 Basic Power Quality Analyzer, without probes, is a versatile instrument designed to analyze and monitor power quality in electrical systems. While it doesn’t come with probes, it can be used with compatible probes and accessories to perform a wide range of power quality measurements. Here are some key features of the Fluke 1773 Basic Power Quality Analyzer:
- Power Quality Analysis: The Fluke 1773 is capable of measuring various parameters related to power quality, including voltage, current, frequency, power factor, harmonics, and flicker. It provides detailed insights into the quality of electrical power within a system.
- High Accuracy Measurements: With high accuracy measurements, the Fluke 1773 ensures reliable data for identifying and diagnosing power quality problems accurately.
- Waveform Capture: The analyzer can capture and record voltage and current waveforms, allowing users to analyze transient events, sags, swells, interruptions, and other anomalies in the electrical system.
- Harmonics Analysis: It can detect and analyze harmonics present in the electrical system, helping users identify harmonic distortion and its potential impact on equipment and performance.
- Data Logging: The Fluke 1773 has built-in data logging capabilities, allowing users to record power quality parameters over time. This feature is useful for long-term monitoring and trend analysis.
- Real-time Monitoring: Users can view real-time measurements and waveforms on the analyzer’s display, enabling quick assessment of power quality conditions.
- Reporting and Analysis Software: The Fluke 1773 comes with software for analyzing recorded data, generating reports, and performing in-depth analysis of power quality issues.
- Remote Monitoring: Some models may offer remote monitoring capabilities, allowing users to access measurement data and analysis remotely via network connections.
- Rugged Design: Built to withstand harsh industrial environments, the Fluke 1773 features a rugged design that ensures durability and reliability in demanding conditions.
Overall, the Fluke 1773 Basic Power Quality Analyzer is a powerful tool for power quality analysis, offering advanced features and capabilities to help professionals maintain and optimize the performance of electrical systems when used with compatible probes and accessories.
Fluke 1773 Basic Packaging Includes:
- FLUKE-1773 Power Quality Analyzer
- FLUKE-17XX flat cable voltage test lead 3-phase+N
- AC285 black alligator clips (set of four)
- AC285 green alligator clip
- Black 1M USB-C cable
- Line cords (US, EU, UK, AUS, BRA)
- FLK-17XX 0.18M test lead set
- Green test lead
- Cable marker set (for voltage and current)
- FLUKE-174X-MA-C8 wall outlet adapter
Fluke 1773 Basic Specifications:
Power quality measurements | ||
---|---|---|
Measured parameter | See operator manual | |
Harmonics | h0 … h50 % fund and RMS for voltage, current and power Phase angles for voltage and current up to h11 |
|
Interharmonics | ih0… ih50 % fund and RMS for voltage and current |
|
Supraharmonics | 2–9 kHz with 200 Hz bins 9–30 khz with 2 kHz bins RMS for voltage and current |
|
Harmonics measurement method | Grouped, sub-grouped and single harmonic bins according to IEC 61000-4-7. Method selected automatically based on configured PQ standard or user configurable. |
|
Total harmonic distortion | Calculated on up to 50 harmonics (depends on selected PQ standard) | |
Mains signaling | 2 frequencies in the range from 110 Hz to 3000 Hz | |
Events | Voltage | Dip, swell, interruption, rapid voltage change, mains signaling, waveshape deviation, transients |
Current | Inrush current | |
Triggered recordings | Half cycle RMS of voltage and current for 10 s Waveform of voltage and current for 10/12 cycles Mains signaling: 200 ms RMS of mains signaling voltage up to 120 s Transients: Waveform of voltage (Fluke 1777: 1 MS/s or 20 MS/s, 500,000 pts, Fluke 1775: 1 MS/s, 25,000 pts) |
Electrical measurement accuracy
Parameter | Range | Resolution | Intrinsic Accuracy at Reference Conditions % of Reading + % of Full Scale |
|
---|---|---|---|---|
Voltage | 1000 V | 0.1 V | 0.1 % of nominal voltage in accordance with IEC 61000-4-30 Class A1,2 ±(0.04 % + 0.004 %)3 |
|
Voltage dips and swells | – | 0.1 V | 0.2 % of Vnom1,2 | |
Voltage transients | ±8 kVpk | – | ±5 % +0.25 %) | |
Voltage harmonics/interharmonics | 100 % | 0.1 % / 0.1 mV | ≥1 % Vnom1:  ±2.5 % of rdg. <1 % Vnom1:  ±0.025 Vnom |
|
THD on voltage | 100 % | 0.1 % / 0.1 V | ±(2.5 % + 0.5 %) | |
Voltage distortions 2-9 kHz | Max 100 V | 0.1 mV | ±(2.5 % + 0.1 V) | |
Voltage distortions 9-30 kHz | Max 100 V | 0.1 mV | ±(2.5 % + 0.1 V) | |
Current (Rogowski clamp mode) |
With iFlex 1500 A, i17XX-FLEX1500 24 |
150 A 1500 A |
0.01 % 0.1 A |
±(1 % + 0.02 %) |
With iFlex 3000 A, i17XX-FLEX3000 24 |
300 A 3000 A |
0.01 A 0.1 A |
±(1 % + 0.03 %) | |
With iFlex 6000 A, i17XX-FLEX6000 36 |
600 A 6000 A |
0.1 A 1 A |
±(1.5 % + 0.03 %) | |
With AC clamp 40 A, i40s-EL |
4 A 40 A |
0.001 A 0.01 A |
±(0.7 % + 0.02 %) | |
With AC clamp 400 A, i400s-EL |
40 A 400 A |
0.01 A 0.1 A |
±(2 % + 0.2 %) ±(0.7 % + 0.1 %) |
|
With AC/DC clamp 2000 A, 80i-2010s-EL |
200 A 2000 A |
0.01 A 0.1 A |
±(0.8 % + 0.2 %) | |
Current min/max | 100 % | defined by accessory | x2 of intrinsic accuracy | |
Current harmonics/interharmonics | 100 % | 0.1 % / 0.01 A | ≥3 % Inom:  ±2.5 % of rdg.4 <3 % Inom:  ±0.15 % of Inom |
|
THD on current | 100 % | 0.1 % | ±(2.5 % + 0.5 %) | |
Frequency | 42.5 Hz … 69 Hz | 0.001 Hz | ±0.01 Hz | |
Voltage unbalance | 100 % | 0.1 % | ±0.15 % | |
Current unbalance | 100 % | 0.1 % | ±0.15 % | |
Flicker Pinst, Pst, Plt | 0 to 20 | 0.01 | 5 % | |
Mains signaling voltage | Up to 3 kHz 0-15 % of Vnom |
0.1 V / 0.1 % | 1-3 % Vnom: ±0.15 % of Vnom 3-15 % Vnom: ±5 % of rdg. |
|
AUX input | ±10 V | 0.1 mV | ±(0.2 % + 0.05 %) | |
1 Nominal voltage in the range of 100 V to 690 V. Also known as Udin. 2 0 °C to 45 °C: Intrinsic Accuracy x2. Outside of 0 °C to 45 °C: Intrinsic Accuracy x3 3 Only for calibration laboratories 4 With iFlex 1500A, I17XX-FLEX1500 24 |
Reviews